E+H Deltabar S PMD70 PMD70-ABA7D2DAAU

$1.00

+ Free Shipping
  • Measuring principle

    Differential pressure

  • Characteristic

    Digital transmitter with ceramic measuring diapragms
    Modular transmitter
    Long-term stability
    Enhanced safety via self diagnostic functions
    Secondary process barrier

  • Supply voltage

    4…20mA HART:
    10,5…45V DC
    Ex ia: 10,5…30V DC
    PROFIBUS PA /
    FOUNDATION Fieldbus:
    9…32V DC

  • Reference Accuracy

    0,075%
    “PLATINUM” 0,05%

  • Long term stability

    0,05% of URL/year
    0,125% of URL/5 years

  • Process temperature

    -20°C…85°C
    (-4°F…185°F)

  • Ambient temperature

    -20°C…85°C
    (-4°F…185°F)

  • Measuring cell

    25mbar…3bar
    (10inH2O…45psi)

  • Max. overpressure limit

    on one side:
    100 bar
    (1500 psi)

  • Process connection

    1/4-18NPT
    RC1/4″

  • Communication

    4…20mA HART
    PROFIBUS PA
    FOUNDATION Fieldbus

  • Certificates / Approvals

    ATEX
    FM
    CSA
    NEPSI
    IECEx

  • Safety approvals

    SIL
    Overfill prevention WHG

  • Design approvals

    EN10204-3.1

  • Marine approvals

    GL

  • Specialities

    diagnostic functions

  • Successor

    PMD75